Voltage stabiliser, 3 phases

last updated : 2019/03/18
Code Description Budget Price Ship. weight Ship. vol.
EELESTAB0015
VOLTAGE STABILIZER, 3 phases independent 400V/230V, 15 KVA CH 2,625.00 0kg 0 Add
EELESTAB0020
VOLTAGE STABILIZER, 3 phases independent 400V/230V, 20 KVA CH 3,150.00 0kg 0 Add
EELESTAB0025
VOLTAGE STABILIZER, 3 phases independent 400V/230V, 25 KVA CH 2,100.00 700kg 1,55m³ Add
EELESTAB0030
VOLTAGE STABILIZER, 3 phases independent 400V/230V, 30 KVA CH 3,150.00 0kg 0 Add
EELESTAB0045
VOLTAGE STABILIZER, 3 phases independent 400V/230V, 45 KVA CH 4,200.00 0kg 0 Add
EELESTAB0060
VOLTAGE STABILIZER, 3 phases independent 400V/230V, 75 KVA CH 5,250.00 0kg 0 Add
EELESTAB0100
VOLTAGE STABILIZER, 3 phases independent 400V/230V, 100 KVA CH 6,300.00 0kg 0 Add
EELESTAB0125
VOLTAGE STABILIZER, 3 phases independent 400V/230V, 125 KVA CH 7,350.00 0kg 0 Add
EELESTAB0150
VOLTAGE STABILIZER, 3 phases independent 400V/230V, 150 KVA CH 7,875.00 0kg 0 Add
EELESTAB0175
VOLTAGE STABILIZER, 3 phases independent 400V/230V, 175 KVA CH 8,400.00 0kg 0 Add
EELESTAB0200
VOLTAGE STABILIZER, 3 phases independent 400V/230V, 200 KVA CH 8,925.00 0kg 0 Add

 

General information

A main power voltage stabilizer is used to improve the quality of the 230 / 400 V power supply used in offices or workshops.  Large variation in the main electrical power supply could damage all the items connected to it (computers, photocopier, motor, machines, etc..).

The capacity of a voltage regulator is given in VA - Volt / Ampere. This value could be calculated from the power consumed in Watt divided by the power factor. While the power factor is equal to one in case of resisting load (heating resistance for example), appliance such as motor or fluorescent lamp degrade this power factor to a lower value (0.7 for example). This impact the voltage regulator which has to be dimensioned to a larger value. It is also possible to correct the power factor using network capacitors.

It is recommended to ask a certified electrician to evaluate the requirements for the voltage regulator power and the optional correction measure.

Line conditioners are an improved version of voltage stabilizer, adding filtering, surge reduction and limit the effect of disturbance on the protected elements. This improve version is the recommended model.

While these types of voltage regulator are sufficient in most cases, large variations of frequency in the main supply could also lead to problems on some of the appliances connected. In such a case an inverter solution could be investigated (see inverter).

Specifications

Line conditioner type.

Independent regulation over three phases

Quick response control system (motor driven variable transformer should be avoided)

Control panel with voltage / current display

Input voltage correction range better than +/- 15% (+/- 30 % recommended)

Power in VA (Volt/Ampere) depending of the needs